We are a service company and we employ technicians.  Our focus is to make sure your generator is running smoothly and will be ready to run when needed.

Our Services Include:

  • Preventative Maintenance Program
  • Warranty Support
  • Repair and Replacement Part Installation
  • Load Bank Testing
  • Installations
Generac Generators
Kohler Generators
Cummins Generators
Yanmar Generators

Our Preventative Maintenance Program includes:

Air System:

  1. 1.   Clean / Replace Air Cleaner Element
  2. 2.   Check Complete Air System for Deficiencies
  3. 3.   Clean / Change Oil in Bath Filter
  4. 4.   Check Turbocharger Shaft End Play
  5. 5.   Check / Tighten Turbocharger Mounting Bolts
  6.  

Lubricating System:

  1. 6.   Change Engine Oil & Oil Filter
  2. 7.   Change Hydraulic Governor Oil
  3. 8.   Clean / Replace Crank case Breather
  4. 9.   Check Complete Engine for Oil leaks
  5. 10. Check PVC Valve
  6.  

Cooling System:

  1. 11. Inspect / Replace All Belts & Hoses
  2. 12. Check / Fill coolant level
  3. 13. Test Specific Gravity of Anti-Freeze
  4. 14. Change Corrosion resistor element
  5. 15. Check Complete System for Coolant leaks
  6. 16. Check Block Heater & Thermostat
  7. 17. Lube Fan Hub
  8.  

Fuel System:

  1. 18. Inspect day tank & fuel inside tank
  2. 19. Check / Replace Fuel Filter(s)
  3. 20. Check Operation of Governor
  4. 21. Clean Fuel Pump Screen
  5. 22. Check Fuel Lines for leaks
  6.  

Electrical System:

  1. 23. Check / Clean & tighten all electrical connections
  2. 24. Check electrolyte level of batteries
  3. 25. Check operation of all sending units
  4. 26. Inspect / Replace points, condenser & plus
  5. 27. Inspect ignition system
  6. 28. Check / Set Timing (Full PM Only)
  7. 29. Check Operation of battery charger; replace blown fuses
  8.  

Other Systems and Checks:

  1. 30. Check oil, start, warm-up, oil pressure
  2. 31. Check Amps & Volts per leg
  3. 32. Check frequency
  4. 33. Adjust frequency & voltage as required
  5. 34. Check Exhaust system for leaks
  6. 35. Check timing sequence on cranking cycles
  7. 36. Check operation of transfer switch
  8. 37. Check engine / Generator controls settings
  9. 38. Start engine from test position
  10. 39. Start engine from automatic position
  11. 40. Check all alarm systems
  12. 41. Inspect / Replace pilot lights
  13.  

© 2020 schwalmgeneration.com   909-815-4631  schwalm_generation@yahoo.com